background image

ROSSMA IIOT-AMS 1-WIRE/ 

OPERATION MANUAL 

 

1

st

 revision 04.09.2019   

4

 

 

1.

 

DESCRIPTION AND OPERATION PRINCIPLE

 

 

SWITCHING DEVICE DESCRIPTION 

ROSSMA  IIOT-AMS  1-WIRE  switching  device  is  designed  to  poll  digital  DS18B20  temperature 

sensor independently using 1-Wire bus and transmit the received data in LoRaWAN® or NBiOT 

network. 

The switching device can be used in industrial enterprises, infrastructure of housing and 

communal facilities, in hard-to-reach places (wells, basements). The switching device provides 

the possibility to install control and measuring devices in places with no power supply, operates 

in difficult climatic and weather conditions. 

 

The switching device is manufactured with a 3.6 V power supply.  

The power cell of the ROSSMA IIOT-AMS 1-WIRE switching device is a built-in battery with a 

capacity of 1200/6000/9000/14000/19000 mAh, designed for up to 10 years service life when 

counting readings and transmitting data once a day. 

 

 

 

 

DATA COLLECTION AND TRANSMISSION ALGORITHM 

Data acquisition via 1-Wire bus is performed discretely according to the specified interval. The 

package with the received data is transmitted in wireless network with a period of 1 minute (it 

is not recommended to set the discreteness to less than 1 minute for long-term autonomous 

operation mode of ). The read data is stored in the switching device memory. 

The data transmission period can be configured from 1 minute. By default, the manufacturer 

sets the data transmission frequency to 1 time/hour. The data is transmitted on the specified 

timer, which is installed in the internal memory of the switching device. 

The  switching  device  is  powered  by  a  built-in  3.6V  power  supply.  The  capacity  of  the  13A/h 

power supply is calculated for the service life according to the table (for example):  

 

ROSSMA  IIOT-AMS  1-WIRE  switching  device  provides  instrument 

functionality from the built-in power supply, allowing to install sensors with 

the  switching  device  in  hard-to-reach  locations  where  no  power  supply  is 

available. 

WARNING: The switching device is equipped with a built-in power cell - a 

non-rechargeable lithium-thionyl chloride (LiSOCL2) battery. 

Attempts to 

charge the battery can cause fire! 

 

Summary of Contents for IIOT-AMS 1-Wire

Page 1: ...MA IIOT AMS 1 Wire OPERATION MANUAL Switching device ROSSMA IIOT AMS 1 Wire is intended for independent polling of DS18B20 temperature digital sensor using 1 Wire bus and for transferring of the obtained data in LoRaWAN or NBiOT network ...

Page 2: ...S 1 Wire Document type Operation manual Document code MAN RIA1W 01 Last revision number and date 04 09 2019 THIS DOCUMENT IS VALID FOR THE FOLLOWING DEVICES LINE NAME DEVICE NAME ROSSMA IIOT AMS 1 WIRE ROSSMA IIOT AMS 1 WIRE ROSSMA IIOT AMS 1 WIRE Ex HISTORY OF DOCUMENT EDITION EDITION DATE COMMENTS 01 04 09 2019 Date of document creation ...

Page 3: ...EFINED DATA ON CERTIFICATION ERROR BOOKMARK NOT DEFINED 2 TECHNICAL CHARACTERISTICS ERROR BOOKMARK NOT DEFINED 3 WORKING WITH THE SWITCHING DEVICE ERROR BOOKMARK NOT DEFINED CONTACTS DESCRIPTION ERROR BOOKMARK NOT DEFINED INITIAL START UP ERROR BOOKMARK NOT DEFINED 4 COMMUNICATIONS PROTOCOL ERROR BOOKMARK NOT DEFINED DATA PACKAGE FORMAT ERROR BOOKMARK NOT DEFINED SWITCHING DEVICE CONTROL AND CONFI...

Page 4: ...ng device produced by ROSSMA LLC and defines installation and connection procedure as well as control commands and functional description The manual is intended for specialists familiar with the installation rules in the field of various electronic and electrical equipment To ensure proper functioning the switching device must be installed and adjusted by qualified personnel ...

Page 5: ... Data acquisition via 1 Wire bus is performed discretely according to the specified interval The package with the received data is transmitted in wireless network with a period of 1 minute it is not recommended to set the discreteness to less than 1 minute for long term autonomous operation mode of The read data is stored in the switching device memory The data transmission period can be configure...

Page 6: ...perature sensors Water leak sensors Voltage sensors Water and gas pressure sensors The switching device is class A device LoRaWAN classification and provides the following functionality ADR Adaptive Data Rate support Wireless configurable LoRaWAN activation type in LoRaWAN network OTAA АВР By default АВР Configurable communication period from 1 minute and more configured remotely over LoRaWAN netw...

Page 7: ...21AB90 Declaration ЕАЭС N RU Д RU АБ93 B 08697 on Compliance with the Technical Regulation Requirements of the Customs Union ТР ТС 020 2011 Electromagnetic Compatibility of Technical Means meets industrial safety requirements Certificate of conformity NoС RU МТЭ OC 001 Н 0003 The housing complies with the Technical Regulation Requirements of the Customs Union ТР ТС 012 2011 On Equipment Safety for...

Page 8: ...unication Period Adjustable in LoRaWAN network LoRa antenna type internal Sensitivity 138 dBm Radio communication range in dense development Up to 5 km Radio communication range in non urban area Up to 15 km Default transmitter power 25 milliwatt adjustable POWER SUPPLY Built in battery capacity specified when ordering 13000 mAh by default External power supply capability yes Power supply of conne...

Page 9: ...he switching device you must connect the battery plug to the terminal on the board The switching device supports two methods of activation in the LoRaWAN network ABP and OTAA By default the manufacturer sets the activation method to АВР You can specify one way by using a special command sent to the switching device in LoRaWAN network ...

Page 10: ...e sign Print 4f value output with 4 decimal places SWITCHING DEVICE CONTROLLING AND PROGRAMMING The switching device receives the following control commands on port 1 or port 2 0x01001E where 0x001E is the new call out interval in seconds not saved when power is reset 0x02001E where 0x001E time in seconds when the switching device communicates next time 0xBB Query the switch version The answer wit...

Page 11: ... shall be stored in the factory package in heated rooms at temperature from 5 С to 40 С and with relative humidity not more than 85 The switching devices can be transported in covered cargo compartments of all types for any distances at temperature from 40 С to 85 С 5 STORAGE AND TRANSPORTATION RULES ...

Page 12: ...ons and rules of transportation storage and operation specified in this user manual The Manufacturer shall not be liable for defects caused by normal wear non compliance with the Manufacturer s requirements in terms of storage installation operation or operating conditions inadequate usage any changes or repairs not previously authorized by the Manufacturer in writing Warranty is not subject to Sw...

Page 13: ...www rossma ru www rossma ru Operation manual Ó ROSSMA LLC 2020 ...

Reviews: