21
7.4.2 P00
User Menu
The User menu shows normal operational values and information displays. This is the default display menu;
no access code is required.
item# description
units step
min
max
default
display
1 information
screen
--- no_edit
--- --- ---
C>
2 delivery
air
temperature
°C/°F no_edit
---
---
---
Td
3 delivery
pressure
bar/psi no_edit ---
---
---
Pd
6 running
hours
h no_edit
0 99999
---
H1
1430
7 loaded
hours
h no_edit
0 99999
---
H2
1275
8 general
service hours
h no_edit
-9999
9999
---
H3
0570
9 air
filter
service hours
h no_edit
-9999
9999
---
H4
0080
10
##
motor speed
rpm
no_edit 0
7200
---
Sr
3000 rpm
11
##
percent speed
%
no_edit 0.0
100.0
---
SP
100.0 %
** only shown if internal pressure sensor function activated
## only shown if variable speed regulation mode is activated (S1-20 only)
Status Information Item:
The page 0 ‘Status Information Item’ provides a basic overview of status using symbols:
Main
motor
running
Compressor
on
load
Delivery pressure relative to pressure set points, not displayed when remote pressure control active.
Pressure equal to, or below, load pressure set point
Pressure equal to, or above, unload pressure set point
Pressure between load and unload pressure set points
Condensate drain valve output is energised (if function enabled)
Countdown timer function is occurring (Run-On-Time, Stop Run-On-Time, Blowdown Time).
During a countdown time function the remaining time in seconds is displayed.