15
x
For the chimney sweep
15 For the chimney sweep
15.1 Data for designing the flue gas pipe
Tab. 15-1 Triple values for chimney design (flue gas flow dependent on
heat output, see fig. 4-6, page 15)
15.2 Emissions measurement
The check measurement can be made by a simply selectable automatic
function (see also "Operating Instructions - ROTEX-RoCon BF Con-
troller").
Ɣ
Depress the exit button for at least 5 secs.
Î
Menu
"Special Level"
is displayed.
Ɣ
Select the programme
"Emission Measurement"
with the rotary
switch.
Ɣ
Confirm the changes with a brief push of the rotary switch.
Î
The following load types are available for selection:
–
Off:
Emission measurement is switched off, any Gas condensing
boiler-connected heat generator that is switched on continues to
be regulated normally.
–
Base Load:
The heat generator is switched on and operated at
the minimum output of the heat generators, irrespective of the set
operating mode.
–
Full Load:
The heat generator is switched on and operated at the
maximum output of the heat generators, irrespective of the set
operating mode.
Ɣ
Select the load type
"Full Load"
using the rotary switch,
but do not
confirm it
.
Î
Display:
"Full Load"
Î
The burner is turned on for 30 min. and is regulated at maximum
load.
Ɣ
Select the load type
"Base Load"
using the rotary switch,
but do not
confirm it
.
Î
Display:
"Base Load"
Î
The modulating gas burner runs at minimum output for 30 mins.
Ɣ
Cancellation and jump back by:
–
Pushing the exit button or rotary switch again
–
Selection of a different menu using the rotary switch and confirma-
tion.
Unit
Burner-
load in
kW
Rated output in kW
Flue gas mass flow in g/s
Flue gas temperature
in °C
Available
pumping
pressure in
Pa
40/30 °C
80/60 °C
Natural
gas E/H
Natural
gas LL/L
Liquefied
petroleum
gas
40/30 °C
80/60 °C
A1 BG 25(F)-e
5.5
6.0
5.5
2.31
2.31
2.09
32
58
30
25.7
27.0
25.0
10.79
10.81
9.77
45
79
200
A1 BG 40(F)-e
8.0
8.5
7.9
3.36
3.37
3.04
34
60
40
30.0
31.4
29.0
12.60
12.62
11.41
43
78
200
35.0
36.6
33.6
14.70
14.73
13.31
45
80
200
42.5
44.2
40.0
17.85
17.88
16.16
48
82
200
Fig. 15-1 Symbolic brief instructions for emission measurement
Emission Measurement
Off
Emission Measurement
Base Load
Emission Measurement
Full Load
Emission Measurement
Full Load
Special Level
Emission Measurement
Manual Operation
©
ROTEX
·
FA
R
O
TEX
A1
B
G
e ·
Su
bj
ect to
ch
an
ge
an
d
cor
rectio
n
·
008
.150
99
44_
03
·
02
/201
4