RTX-IOM-PRODUCT-YY
Page
65
of
131
www.rotexautomation.com
Function of Input 1
Applicable for Posidapt
–
Modern, Expert, Super, Ultra and IPST
These parameters are used to determine the action based on function of input. The direction
of action can be adapted to normally open or normally close depending upon the sub-
parameters.
•
Off -
Factory default
This valve deactivates the parameter. No function.
•
Message only (NO/NC)
Binary messages from peripherals, e.g. from pressure or temperature switches, can be read
over the communication interface or fed through a logical OR combination with other
messages to trigger the fault message output.
•
Block Configuration (NO/NC)
This parameter value can lock the "configuration" operation mode against reconfiguration.
The lock can be made active by installing a jumper between INP1 terminals.
•
Block configuration & manual mode (NO/NC)
–
(not applicable for IPST)
If input 1 is activated, then manual mode is also blocked in additional to the configuration
operation mode.
•
Block Movement (NO/NC)
–
(not applicable for IPST)
If input 1 is activated, then the movement of the actuator is block to the last position.
Summary of Contents for Posidapt Expert
Page 7: ...RTX IOM PRODUCT YY Page 7 of 131 www rotexautomation com 1 2 Posidapt Series...
Page 17: ...RTX IOM PRODUCT YY Page 17 of 131 www rotexautomation com 4 Bock Diagram...
Page 18: ...RTX IOM PRODUCT YY Page 18 of 131 www rotexautomation com 5 Dimensional Drawing...
Page 44: ...RTX IOM PRODUCT YY Page 44 of 131 www rotexautomation com 7 Electrical Connection...
Page 46: ...RTX IOM PRODUCT YY Page 46 of 131 www rotexautomation com...
Page 79: ...RTX IOM PRODUCT YY Page 79 of 131 www rotexautomation com...
Page 122: ...RTX IOM PRODUCT YY Page 122 of 131 www rotexautomation com...