Move valve position to open (NO/NC)
If input 1 is activated, then the actuator regulates to the
value specified in parameter “End
point soft stopper”.
•
Move Valve position to close (NO/NC)
If input 1
is activated, then the actuator regulates to the value specified in parameter “Zero
point soft stopper”.
•
Move Valve position to user set point (NO/NC)
–
(not applicable for IPST)
If input 1 is activated, then the actuator regulates to the value set by user. The Value can set
from 0.0 to 100%.
•
Partial Stroke test (NO/NC)
Using input 1, a partial-stroke test can be triggered by actuation of your choice of a normally
closed or normally open switch. For this function, the parameter in “Partial stroke test” should
be selected to “Input”.