8.3.3.
Advanced Setup
Input Signal
Range Of Input Signal
Applicable for Posidapt
–
Modern, Expert, Super, Ultra and IPST
This parameter is used to set the current range. The selection of the current
range depends on the type of connection.
•
4-20 mA -
Factory default
Use this parameter when the supply input signal current range is from 4-20 mA.
•
0-20 mA
Use this parameter when the supply input signal current range is from 0-20 mA. This selection
is only possible for 3-4 wire system. Externally 24 VDC supply required.
.