1355 - 1505 CYCLONE VERTICAL MIXER OPERATION
If the PTO is below PTO speed, set at1850 RPM, line 4 will
display
“RUN RPM LOW”
. If the Mix or Feed button is held
“LOW”
will blink.
If there is a fault “
F,L,T”
will blink on the right side of the
display. Use the Up switch to go to the last three display
pages to see the active fault. See fault section below. Cycle
control power to clear a held fault.
Press and hold Clean and Limp buttons for 5 seconds. The
left and right LED of both switches will blink. When the center
LED of both switches start to blink the augers will run at a
slow speed. Press either button to shut off warm up.
Warm Up Operation:
Mixing Mode Operation :
When PTO speed is above the PTO RPM required for mix
the screen will show “Mix RPM OK or if above the required
feed RPM, it will show “Feed RPM OK”.
When PTO speed is above the PTO RPM required to mix,
the screen will show
“MIX RPM OK”.
Press the Mix push button. The augers will start rotation
based on the PTO command speed. The center LED will be
on during mix. Press Stop button to shut off.
If the PTO RPM drops due to engine droop below the command RPM, set at 1850, the PID will
start to reduce the pump output. As engine RPM recovers the PID will increase pump output and
auger speed. The motors will start in maximum displacement. If both motors hydraulic pressure
are below shift pressure, set at 2000 psi, for a time period set at 5 seconds; control will do a switch
to minimum displacement operation. The auger speed PID will maintain 38 to 40 RPM. If either
motor hydraulic pressure is working above shift pressure, set at 4000 psi for a time period set at 5
seconds; control will do a switch to maximum displacement operation.
MAX DISP
MIN DISP
Display page 2: Use Screen Up/Dn
Switch to display auger pressure.