8.1.2 Activating / deactivating acoustic signals
1. Unlock and open the door.
2. With the door open, lock the lock using the key.
3. Press and hold the radio calibration push-button
[1] for 25 - 30 seconds.
Eneo C | CC confirms:
■
Activation of the acoustic signals with a long beep.
■
Deactivation of the acoustic signals with two
beeps in quick succession.
Eneo C | CC exits this mode automatically.
1
8.1.3 Fault assistance
Fault
Cause
Fault rectification
System not functioning
Eneo C | CC | CF is not responding, no
acoustic signals
There is no 230 V voltage at the power
supply unit on the primary side.
Have electrical installation work carried out by qualified
personnel only, as described in the installation instruc-
tions.
There is no 24 V voltage on the secondary
side of the power supply unit.
Check the terminal contacts on the power supply unit.
There is no 24 V voltage on the Eneo C | CC
| CF.
Check the supply line between the power supply unit
and Eneo C | CC | CF, and replace if necessary.
There is 24 V voltage on the Eneo C | CC |
CF unit, but + / - has been mixed up.
Swap round the power supply on the secondary side of
the power supply unit.
The drive is in a final position and does not
receive a signal to implement a movement.
Check the signal lines.
Still not working?
Disconnect the voltage, wait for 10 seconds and restart
it.
Carry out a test using the Eneo Control Unit.
Contact qualified personnel.
Eneo C | CC | CF does not lock automatically
Door is not fully closed.
Close the door fully.
Eneo is in day operation mode.
Change over to night operation mode (input 2 must not
be set to 24 V for night operation mode).
Magnetic striker is incorrectly adjusted.
Check the position of the magnet and adjust if
necessary.
Eneo C | CC | CF does not lock completely
(fault message)
Door or strikers not set correctly (excess
current fault message: Eneo beeps three
times).
Adjust the door or strikers (see “Commissioning”).
Foreign object in striker (excess current fault
message: Eneo beeps three times).
Remove the foreign object.
Latch does not engage correctly and the
door opens again slightly (reed contact not
closed fault message: Eneo beeps twice).
Open the door electrically and push it into the latch
again.
Eneo C was actuated by cylinder.
When a door has been unlocked manually, it must also
be locked again manually (see “Commissioning”).
Commissioning and operation
Eneo C | CC | CF
Activating / deactivating acoustic signals