background image

INFO

The Eneo AF multipoint locking system
requires lever handle hardware to be used
with a set in a combined knob and lever
handle design (see CTL_86).

The lever handle must be positioned at a
height of between 900 mm and 1100 mm.
The installation company is responsible for
any deviations from this.

Fault assistance

Fault

Cause

Corrective action

System not functioning.

Roto Safe Eneo does not respond, no
beeps.

There is no 230 V voltage at the power supply
unit on the primary side.

Have electrical installation work carried out by
qualified personnel.

There is no 24 V voltage on the secondary side of
the power supply unit.

Check the terminal contacts on the power supply
unit.

There is no 24 V voltage on the multipoint
locking system.

Inspect the supply line between the power supply
unit and multipoint locking system and replace if
necessary.

There is 24 V voltage on the multipoint locking
system but the polarity is the wrong way round.

Swap round the power supply on the secondary side
of the power supply unit.

The drive is in a final position and does not
receive a signal to implement a movement.

Inspect signal lines or modify the distance to the
multipoint locking system (distance 1 – 2 m).

Still not working?

Disconnect the voltage, wait for 10 seconds and
restart it.
Carry out a test using the Eneo Control Unit.
Contact qualified personnel.

Roto Safe Eneo does not lock automati-
cally.

Door is not fully closed.

Close the door fully.

Multipoint locking system is in day operation
mode.

Change over to night operation mode (input 2 must
not be set to 24 V for night operation mode).

Rebate magnet is adjusted incorrectly.

Check the position of the magnet and adjust if
necessary.

Adjust the door as required.

Roto Safe Eneo does not lock fully
(without fault message).

Door or strikers not set correctly.

Adjust the door or strikers.

Foreign object in striker.

Remove the foreign object.

Latch does not engage correctly and the door
opens again slightly.

Open the door electrically and push it into the latch
again. Readjust the electrical opener if necessary.

Multipoint locking system was actuated by
cylinder.

When a door has been unlocked manually, it must
also be locked again manually.

Roto Safe Eneo does not lock fully (with
fault message).

Door or strikers not set correctly (3x two-tone
beeps – fault message: excess current).

Adjust the door or strikers.

Foreign object in striker (3x two-tone beeps –
fault message: excess current).

Remove the foreign object.

Door does not unlock.

No signal at the signal transmitter output or no
signal at the multipoint locking system input.

Calibrate the hand-held transmitter (see IMO_438).
Check settings and access control system.
Refer to the operation instructions for the access
control system

Roto Safe Eneo

Subject to change.

Roto Safe Eneo

SUG_11_EN_v0

 · 

04 / 2019

 · 5

 

Summary of Contents for Safe Eneo Series

Page 1: ... out work when the power supply is disconnected Technical data Roto Safe Eneo drive Voltage 24 V DC 5 2 5 A SELV output voltage according to EN 60950 1 Continuous current consumption 25 mA Current consumption 1 5 A peak 2 3 A Relative air humidity 93 Temperature 25 to 60 C transport 25 to 70 C Output relay load Max 40 mA flyback diode for inductive load present internally Standards EN 60 730 1 EN ...

Page 2: ...not connected not connected green green green yellow white white white white EZ cable 3m insertable cable junction on the sash on the frame power supply Eneo Switch IN 100 240V AC OUT 24V DC 2 5A plug cable assignment white IN1 Input 1 open brown 24V green GND yellow not connected grey not connected pink not connected Roto Safe Eneo 2 04 2019 SUG_11_EN_v0 Roto Safe Eneo Subject to change ...

Page 3: ...ight operation mode This can be used as an option Terminals 5 and 6 are connected to one another internally via a relay and a 47 ohm resistor The maximum load of the contacts is 24 V 40 mA Maximum line lengths Eneo cable junction insertable 180 incl 4 m cable with round connector for Eneo Control Unit up to power supply unit From Eneo cable junction connector Up to 4 m Up to 10 m Up to 20 m Up to ...

Page 4: ...pproximately 2 seconds Unlocking the door from the outside Depending on the access control system available unlocking can be triggered by hand held transmitter finger scan Phone Code etc INFO If the deadbolt is locked the lock cannot be opened electronically Unlocking the door from the inside The Eneo C multipoint locking system can only be unlocked using a key or electrical signal e g push button...

Page 5: ...ing the Eneo Control Unit Contact qualified personnel Roto Safe Eneo does not lock automati cally Door is not fully closed Close the door fully Multipoint locking system is in day operation mode Change over to night operation mode input 2 must not be set to 24 V for night operation mode Rebate magnet is adjusted incorrectly Check the position of the magnet and adjust if necessary Adjust the door a...

Page 6: ...ioned adjusted correctly Lock the door again Position the magnet correctly and lock the door again 3x two tone beeps Fault Control unit detected excess current in the motor and stopped Remove blocks If the door is not running smoothly contact the door manufacturer 4x two tone beeps Fault The final position of the connecting rod was not reached in the maximum permitted time of 3 seconds No movement...

Page 7: ...Str 21 A 8401 Kalsdorf bei Graz Austria Notausgangsverschluss lt EN179 E611 LE DoP Nr KD Door E611 Nr 001 CPR 2016 05 17 16 EN 179 2008 04 Notausgangsverschluss mit Drückerbetätigung Typ A für Türen in Rettungswegen für außen und innen öffnende Türen n e d n a t s e b e b a g i e r F r u z t i e k g i h ä F 1sec W 100mm A 70N Dauerfunktionstüchtigkeit hinsichtlich der Fähigkeit zur Freigabe gegenü...

Reviews: