24
Installation & Maintenance
Instructions
7.0 Basic Setup
X
7.5 Set Output Thrust (cont'd)
If the Close Thrust value requires adjustment
press ENTER.
The actuator is now in EDIT Mode and the parameters
can be modified.
Use the UP/DOWN buttons until the correct Thrust Value is
displayed.
Press ENTER to save the changes. Visually confirm that the
parameter is saved.
Press CANCEL to return to previous menu.
Use UP/DOWN buttons until THRSTO is displayed.
Press ENTER to view the Open output Thrust set value.
The Thrust Output is adjustable between 60% and 150% of
its rated value.
Fig 7.12 shows the Opening Thrust value set to 100% of its
rated value.
Press ENTER to change the Open Thrust set value.
NOTE: When the Thrust is selected above the 100%
Rated value this additional effort is only available at
the end of travel to seat the valve for tight shut off
applications.
NOTE: The output Thrust setting must be sufficient
to operate the valve under full working process
conditions.
X
X
X
LOCAL
THRSTO
X
LOCAL
TO 100
%
VIEW
LOCAL
TC 600
%
EDIT
LOCAL
TC 700
%
EDIT
LOCAL
SAVED
VIEW
X
Fig 7.8
Edit close thrust value
Fig 7.9
Edit close thrust value
Fig 7.10 Save new value
Fig 7.11 Open thrust setting
Fig 7.12 View open thrust value