30
Installation & Maintenance
Instructions
7.0 Basic Setup
LOCAL
CMD 4
X
X
X
X
EDIT
LOCAL
POS I T
LOCAL
POS I T
LOCAL
EDIT
CMD 4
LOCAL
SAVED
EDIT
7.9.2 Calibrate Command Signal Zero Setpoint Using
an External 4-20 mA Signal
Press the DOWN arrow until the CMD 4 menu is displayed.
Press ENTER until ‘EDIT’ is displayed.
Apply LOW setpoint signal (4 mA).
Press ENTER.
The actuator Zero setpoint is automatically calibrated to the
applied analogue signal.
Press CANCEL to go back to top level menu.
STEP 1
SELECT LOCAL
OPERATION
STEP 2
SET OUTPUT
THRUST
STEP 4
SET CLOSE LIMIT
OF TRAVEL
STEP 5
SET OPEN LIMIT
OF TRAVEL
STEP 6
CALIBRATE COMMAND
SIGNAL ZERO SETPOINT
STEP 7
CALIBRATE COMMAND
SIGNAL SPAN SETPOINT
STEP 3
SELECT ACTION AT END
OF TRAVEL (LIMIT OR FORCE)
STEP 8
DEADBAND
Fig 7.33 Default display
Fig 7.34 Low command setting
Fig 7.35 Edit low set point signal
Fig 7.36 Save low set point signal
Fig 7.37 Default display