36
Installation & Maintenance
Instructions
8.0 Status Alarm Menu
R1 ENR
R1 ENR - Relay 1 Energised
R2 ENR
R2 ENR - Relay 2 Energised
DITHER
DITHER - Dither
Notification is generated when the actuator has performed
more than 3,600, 1% position changes (or starts) per hour.
EE FLT
EE FLT - EEPROM Parameters
EEPROM parameters out of range.
Actuator is disabled , restore defaults and check basic and
advanced parameters.
EC FLT
EC FLT - EEPROM Fault Customer Defaults
Customer defaults stored incorrectly or corrupted in the
EEPROM. Actuator runs. Cycle the power and restore the
customer defaults to remove the alarm.
EF FLT
EF FLT - EEPROM Factory Defaults
Actuator runs. Cycle power to remove the alarm. If problem
persists contact Rotork.
STALL TIME
CPT 20
CMD SRCE
CPT 4
INFO
SPLT RANGE
RELAYS
ACT CFG
ADVANCED
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust or Torque
LOCREM
Local / Remote Control
MANJOG
Manual Jog
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CFG
Control Setup
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
BASIC
INFO
ACT STS
AMP STS
TEMP
SWR VER
CTR SETUP
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LOW
LOS HI
TORQ O
TORQ C
CL ACT
OP ACT
RELAYS
RLY1 CFG
RLY1 POS
RLY1 FRM
RLY2 CFG
RLY2 POS
RLY2 FRM
ACT CFG
ACT TYPE
ACT SIZE
ENCOD IN
ASRACT
SP RANGE
MIN CMD
MAX CMD
BSRACT
ST CUST
LD CUST
DEFAULTS
LD FACT
OVTEMP
OVTEMP - Over Temperature
Internal Temperature Sensor Tripped.
LOSCOM
LOSCOM - Loss of Remote Bus Communications
Loss of serial bus communications greater than the COM TO
communications time out period has occurred.
LOCAL
LOCAL - Local Control Selected
Actuator is selected for Local Operation. The actuator will
not respond to remote commands. Local operation must be
selected to modify parameters.
CL LIM
CL LIM - At Closed Limit
The actuator position is at or below the closed end of
travel limit.
OP LIM
OP LIM - At Open Limit
The actuator position is at or above the open end of
travel limit.
ESD
ESD - Emergency Shutdown active
Emergency Shut Down (ESD) command is active. The actuator
will not respond to any other commands until the ESD
condition is removed.
MONRLY
MONRLY - Monitor Relay Tripped
Monitor Relay tripped and actuator is not available for
remote control.
8.1 Status Indication (cont'd)
A4
US
US
A4
US
A4
US
A4