38
Installation & Maintenance
Instructions
9.0 Fault History Menu
STALL TIME
CPT 20
CMD SRCE
CPT 4
INFO
SPLT RANGE
RELAYS
ACT CFG
ADVANCED
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust or Torque
LOCREM
Local / Remote Control
MANJOG
Manual Jog
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CFG
Control Setup
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
BASIC
INFO
ACT STS
AMP STS
TEMP
SWR VER
CTR SETUP
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LOW
LOS HI
TORQ O
TORQ C
CL ACT
OP ACT
RELAYS
RLY1 CFG
RLY1 POS
RLY1 FRM
RLY2 CFG
RLY2 POS
RLY2 FRM
ACT CFG
ACT TYPE
ACT SIZE
ENCOD IN
ASRACT
SP RANGE
MIN CMD
MAX CMD
BSRACT
ST CUST
LD CUST
DEFAULTS
LD FACT
9.1 Fault History (cont'd)
CMA FAULT HISTORY STRING DEFINITIONS
FAULT
STRING
DESCRIPTION
At Close Limit
CLL
The actuator was at or below the CLOSE LIMIT setting.
At Open Limit
OPL
The actuator was at or above the OPEN LIMIT setting.
ESD Active
ESD
The Emergency Shut Down (ESD) feature was activated.
Dither
DIT
The unit has exceeded 3,600 starts per hour where the change in
position is greater than 1% of travel.
Relay One Energized
R1
Relay one is energized.
Relay Two Energized
R2
Relay two is energized.
EEPROM Fault, params
EE
An error was found in the current parameter area of the EEPROM.
EEPROM Fault, customer
CEE
An error occurred when the customer defaults were stored.
The actuator will still run but the customer defaults should be
checked and reconfigured if necessary. Save any changes before
cycling the power. Cycling the power will clear the fault, contact
Rotork if the problem persists.
EEPROM Fault, factory
FEE
An error occurred when the Factory defaults were stored.
The actuator will still run but the Factory defaults should be checked
and resaved. Cycling the power will clear the fault, contact Rotork if
the problem persists.
Reset RST
The actuator was reset (power cycled).
Monitor Relay
MNR
The actuator was not available for proper remote operation
(General or Critical Fault).
Local Control Knob Stop
LCS
The local control knob was set to the LOCAL STOP position.
Local Control Knob
Remote
LCR
The local control knob was set to the REMOTE position.
Local Control Knob
LCL
The local control knob was set to the LOCAL STOP position.
Local
Loss of Power
LOP
Loss of power occurred. Units with RPP only.
Charge Mode
CHG
Charge Mode initiated. Units with RPP only.
A4
US
US
A4
US
A4
US
A4