Keeping the World Flowing
41
10.0 Default Menu
10.2.4 Control Configuration Menu
PARAMETER
DEFAULT VALUE
Control Algorithm
Open loop
Input Dampening
0 seconds
Input Signal Loss Time out
0 seconds
Input Signal Loss Action
Close
Input Signal Loss Position
50%
Input Signal Loss Low Level
3.6 mA
Input Signal Loss High Level
20.4 mA
TORQ O
100%
TORQ C
100%
CL ACT
LIM
OP ACT
LIM
10.2.5 Relays 1 & 2 Menu
PARAMETER
DEFAULT VALUE
Relay 1 Config
None
* Relay 1 Pos
25%
Relay 1 Form
Energize on Condition
Relay 2 Config
None
* Relay 2 Pos
75%
Relay 2 Form
Energize on Condition
* Only shown when configured as Drive to Position (won’t be configured for position on default)
10.2.6 Split Range Menu
PARAMETER
DEFAULT VALUE
Lower Range Value
4 mA
Upper Range Value
20 mA
CMD Below Split Range Action
Disabled - no action
CMD Above Split Range Action
Disabled - no action
10.2.7 Actuator Config Menu
PARAMETER
DEFAULT VALUE
Actuator Type
Set at Factory to match actuator build
Actuator Size
Set at Factory to match actuator build
Encoder Initialization
Set at Factory at middle of travel
10.2.8 UPS Menu
PARAMETER
DEFAULT VALUE
Loss of Power Action
Disabled - No action
Loss of Power Position
50%
Loss of Power Time out
0 Seconds
Loss of Power Speed
100%
Override Remote Control
ON - Loss of power action overrides remote control
Override Local Control
OFF - Local control overrides loss of power action
Override Local Stop Control
OFF - Local Stop control overrides loss of power action
A4
US
US
A4
US
A4
A4
US