46
Installation & Maintenance
Instructions
11.0 Advanced Menu
RELAYS
11.2.8 RELAYS
There are two configurable relays mounted on the main PCB.
R1(2) CFG - RELAY 1(2) CONFIGURATION
The menu structure is the same for both relays. 1C or 2C
denotes which relay menu is active.
DIO - DIGITAL INPUT AND RELAY OUTPUT OPTION PCB
(If Fitted)
The DIO option pcb provides an additional 4 configurable
Relays R5 to R8.
These relays have the same functions and method of
Configuration as Relays R1 and R2.
Relay Indication functions are as follows:
NON
No Function
POS
Intermediate position indication. If selected then
an additional POS menu is available. Go to R1(2)
POS menu, select and save the position in travel
at which the relay is to activate
GNF
General Fault
CMD
Loss of Command Signal
LFB
Loss of Feedback Signal
STO
Motor Stalled in Open Direction
STC
Motor Stalled in Closed Direction
OTH
Open Thrust Overload
CTH
Close Thrust Overload
OTP
Over Temperature
COM
Loss of Bus Communications
LOC
Local Selected
CLL
Closed Limit
OPL
Open Limit
ESD
Emergency Shutdown Active
CRF
Critical Fault
DIT
Dither
Exceeding 2000 1% position changes per hour
MNR
Monitor Relay Active (Available)
LOP
Loss of Power
CHG
Charge Mode
UPS
UPS Error
DIG
Energised by Bus Command
RELAYS
R1 CFG - Relay 1 Config
R1 POS - Relay 1 Pos
R1 FRM - Relay 1 Form
R2 CFG - Relay 2 Config
R2 POS - Relay 2 Pos
R2 FRM - Relay 2 Form
R5 CFG - Relay 5 Config
R5 POS - Relay 5 Pos
R5 FRM - Relay 5 Form
R6 CFG - Relay 6 Config
R6 POS - Relay 6 Pos
R6 FRM - Relay 6 Form
R7 CFG - Relay 7 Config
R7 POS - Relay 7 Pos
R7 FRM - Relay 7 Form
R8 CFG - Relay 8 Config
R8 POS - Relay 8 Pos
R8 FRM - Relay 8 Form
SPEED
CPT 20
CPT 4
INTTIM
ADVANC
INFO
ST ACT
AMP ST
TEMP
SW VER
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust Display or
Ouput Torque
LOCREM
Local / Remote Operation
MANJOG
Manual Jog
TORQ/THRSTC
Close Torque/Thrust
TORQ/THRSTO
Open Torque/Thrust
CL ACT
Close Action
OP ACT
Open Action
BASIC
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
CTRCFG
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LO
LOS HI
ACTCFG
RELAYS
R1 CFG
R1 FRM
R2 CFG
R2 POS
ACTTYP
ACTSIZ
ENCINI
SPLTRG
MINCMD
MAXCMD
BSRACT
ASRACT
ASPOS
BSRPOS
UPS
LOP AC
LOP PO
LOP TO
OR REM
OR LOC
OR LST
LOP SP
DEFLTS
LD CUST
ST CUST
LD FACT
R2 FRM
R1 POS
R5 CFG
R5 FRM
R6 CFG
R6 POS
R6 FRM
R5 POS
R7 CFG
R7 FRM
R8 CFG
R8 POS
R8 FRM
R7 POS
COMMS
MODBUS
PROFIBUS
PAKSCAN
HART
FFBUS
COM TO
LOS ACT
LOS PO
MIN SP
MAX SP
D1 CFG
D2 CFG
D2 FRM
D3 CFG
D3 FRM
D4 CFG
D4 FRM
D1 FRM
DIG IN
PRM OC
Primary Option
RI CTL
Remote Control Inputs
2W PRI
2 Wire Priority
LOS AC
RIRO Only
LOS PO
RIRO Only
ESDACT
ESD Action
ESDOLS
ESD Override Local Stop
KNBMNT
Local Maint
CMDSRC
CMD SRCE
INFO
RELAYS
DIG IN
SPLTRG
ACT CFG
UPS
COMMS
CTRCFG
Control Setup
CMDSRC
STL TO
TURNS***
OP DIR***
INTTIM
CL TIE
ST CLS
SP OPN
CL OFF
ST OPN
SP CLS
OP ON
OP OFF
CL ON
OP TIE
Namur 107
7MN
Maintenance Alarm
7OS
Out of specification Alarm
7FC
Function check Alarm
7FL
Failure Alarm
R1(2) POS
Select Position Here
R1(2) FRM
Relay Form
EOC
Energise on Condition Active
(Normally Open Contact)
DOC
De-energise on Condition Active
(Normally Closed Contact)
A4
US
US
A4
US
A4
US
A4