Non-Hazardous and Hazardous Certified Enclosures
All CMA actuator hazardous and non-hazardous area
enclosures are watertight to IP66, IP67* and NEMA 4.
CMA actuators are available with the following enclosure
types for which the ambient working temperature ranges
are stated.
The limits of frequency of operation are a function of the load
on the actuator and the ambient temperature.
Under the heaviest load at the highest temperature the
capability is up to 3,600 per hour. Favourable load conditions
enable unrestricted starts per hour.
Option temperatures use different actuator components,
please specify temperature requirement. Hazardous area
approvals for other country standards are available; please
contact Rotork.
CMA Range actuators are built in accordance with the
following standards:
3.1 Non-Hazardous Area Enclosures
3.2 Hazardous Area Enclosures
3.0 Approvals
WT: Standard Watertight
Standard
Rating
Standard Temperature
Low Temperature Option
BS EN 60529 (1992)
IP66/67, IP68*
-30 to +70 °C (-22 to +158 ºF)
-40 to +60 °C (-40 to +140 ºF)
NEMA (US)
4 & 6
-30 to +70 °C (-22 to +158 ºF)
-40 to +60 °C (-40 to +140 ºF)
FMC (Canadian)
4 & 6
-30 to +70 °C (-22 to +158 ºF)
-40 to +60 °C (-40 to +140 ºF)
*CML-1500 and CML-3000 are IP68 7m for 72 hours
European ATEX Directive: CE 2809
Directive/Standard
Rating
Standard Temperature
Low Temperature Option
Directive = 2014/34/EU
II 2GD c
-20 to +65 °C (-4 to +150 ºF)
-40 to +60 °C (-40 to +140 ºF)
Standard = EN 60079-0
EN 60079-1, EN 60079-31
EN 13463-1, EN 13463-5
Ex db IIB T4 Gb
Ex tb IIIC T85°C Db
Units fitted with UPS or HMI option
-20 to +60 °C (-4 to +140 ºF)
International Hazardous Area IECEx
Directive/Standard
Rating
Standard Temperature
Low Temperature Option
No Directive
II 2GD
-20 to +65 °C (-4 to +150 ºF)
-40 to +60 °C (-40 to +140 ºF)
Standard = IEC 60079-0
IEC 60079-1, IEC 60079-31
Ex db IIB T4 Gb
Ex tb IIIC T85°C Db
Units fitted with UPS or HMI option
-20 to +60 °C (-4 to +140 ºF)
USA Hazardous Area – Factory Mutual (FM) Certified Explosionproof to NEC Article 500
Class
Division
Group
Standard Temperature
Low Temperature Option
I
1
C, D
-20 to +65 °C (-4 to +150 ºF)
Units fitted with UPS or HMI option
-20 to +60 °C (-4 to +140 ºF)
-40 to +60 °C (-40 to +140 ºF)
II
1
E, F, G
Enclosure types 4, IP66/67/68
Canadian Hazardous Area – Factory Mutual Canada (FMC) Certified Explosionproof to Canadian Electrical Code (CEC)
Class
Division
Group
Standard Temperature
Low Temperature Option
I
1
C, D
-20 to +60 °C (-4 to +140 ºF)
Units fitted with UPS or HMI option
-20 to +60 °C (-4 to +140 ºF)
-40 to +60 °C (-40 to +140 ºF)
II
1
E, F, G
Directive/Standard
Rating
Standard Temperature
Low Temperature Option
Standard =
CSA C22.2 60079-0,
CSA C22.2 60079-1,
CSA C22.2 60079-31
Ex db IIB T4 Gb
Ex tb IIIC T85ºC Db
-20 to +60 °C (-4 to +140 °F)
Units fitted with UPS or HMI option
-20 to +60 °C (-4 to +140 °F)
-40 to +60 °C (-4 to +140 °F)
Enclosure types 4, IP66/67/68
A4
US
US
A4
US
A4
A4
US