5
Open Limit
Open
The Red LED will be lit, the open symbol
and "Open Limit" will be displayed.
Fig. 3.3
Mid Travel
The Amber LED will be lit, percentage
open value will be shown and "Stopped"
will be displayed when there is no
actuator movement.
Fig. 3.4
Closed
The Green LED will be lit, closed symbol
and "Closed Limit" will be displayed.
Fig. 3.5
LED Indicators
WARNING: Mid Travel LED
colour may be affected by viewing
angle and lighting level.
The Close LED colour can be changed
to red if required.
Refer to section 9.3.
3.3 Display Status Indication
– Travel
The EH display provides real time
status indication. The top line of the
text display is reserved for travel status
indication. Fig 3.6 shows the travel
status example
Closed Limit
.
Fig. 3.6
Available travel status conditions displayed:
•
Closed Limit
Actuator has reached the
set closed limit position.
•
Open Limit
Actuator has reached the
set open limit position.
•
Moving Open
Actuator is traveling in
the open direction.
•
Moving Closed
Actuator is traveling in
the closed direction.
•
Stopped
Actuator has stopped in a
mid travel position, indicated in the
top display (%open).
•
Timer Active
Interrupter Timer option
enabled only. Interrupter Timer has
stopped the actuator mid travel for a
period equal to the set Timer Off
time.
Refer to section 9.8.
3.4 Display Status Indication
– Control
The bottom line of the text display is
reserved for control status indication
and is displayed for approximately 2
seconds after the control mode or
signal is applied. Fig 3.7 shows the
control status example
Remote Control
.
Fig. 3.7
Available control status conditions displayed:
•
Local Control
Local control selected.
•
Local Stop
Local stop selected.
•
Remote Control
Remote control
selected.
3
Operating your EH Actuator
continued
Closed Limit
Stopped
Closed Limit
Closed Limit
Remote Control