16
7
Commissioning
continued
Setting Tool Battery Replacement
Battery status can be checked by
looking at the Infrared transmitter
window while depressing any Setting
Tool button. A flashing red indicator
should be seen.
Battery replacement must be
carried out in a safe area. To replace
the battery remove the six caphead
screws in the back of the Setting
Tool. Remove the back cover to
expose the battery.
The Setting Tool (old version):
In order to maintain hazardous
area certification fit only Duracell
mN1604 or Rayovac Alkaline
maximum NoAL-9V battery types.
The Setting Tool Pro:
In order to maintain hazardous
area certification fit only with
the following AA size, Alkaline-
Manganese, approved battery types:
Duracell, Coppertop, type MN1500
Duracell, Procell, type MN1500
GP, Super Alkaline, type GP15A
Other types of AA size batteries,
including Duracell, Ultra, type
MN1500, must not be fitted.
The Rotork Bluetooth
®
Setting
Tool Pro:
In order to maintain hazardous
area certification fit only with
the following AAA size, Alkaline-
Manganese or Zinc-Manganese
approved battery types:
Duracell, Procell, type MN2400
Energizer, type E92.
Refit cover ensuring red indicator
LED faces the transmitter window in
the back cover.
When a button is depressed the Setting
Tool transmits the relevant instruction
to the actuator by infrared pulses and
must therefore be directly in front of
the actuator indicator window and at a
distance no greater than 0.75m.
The enclosure of the Rotork Setting Tool
Pro
, and Rotork
Bluetooth
®
Setting Tool
Pro
, is manufactured from the following
materials:
Polycarbonate, ABS blend
Polycarbonate
Silicon Rubber
If the Rotork Setting Tool
Pro
and Rotork
Bluetooth
®
Setting Tool
Pro
are likely
to come into contact with aggressive
substances (e.g. solvents that may affect
polymetric materials), then it is the
responsibility of the user to take suitable
precautions (e.g. regular checks as part
of the routine inspections or establishing
that the materials are resistant to the
specific chemical) that prevent it from
being adversely affected, thus ensuring
that the type of protection is not too
compromised.
No form of repair must be
attempted on any of the actuator
Setting Tools.
Download / Upload Function
This new feature has been introduced
with the new Rotork
Bluetooth
®
Setting
Tool
Pro
. It allows the user to download
datalogger files and download/upload
configuration files. The new tool is
weatherproof and intrinsically safe and
so it can be used safely in all environments.
Refer to Bluetooth
®
Setting Tool Pro
publication PUB095-001
.
Display Set-Up Mode
The Setting Tool and Setting Tool arrow
keys are used to access and navigate
through the actuator set-up procedure
using the actuator display. Each actuator
function with it's current setting is
represented on screen by a combination
of code and text.
The Setting Tool change keys (+ and
–) allow the user to view the available
setting options.
The examples of displayed functions
Close Action
,
[C2]
and
Open
Pressure
,
[OP]
are shown above.
Note that a setting option or value is
highlighted.
This instruction manual uses both code
and text for description.
Close Action
Stop on Pressure
Open Pressure
at Limit 90%
Function
Code
Function
Setting
Code
Setting
Option
Function
Code
Function
Setting
Value
Setting
Value