31
If function
[Po]
Position % Open,
is selected and it is configured as a
normally open contact it will make at
the set value with the actuator moving
in the open direction.
To change the form press the
+
or
-
key until the required setting is
displayed.
[nO]
Normally Open (Default):
[nC]
Normally Closed:
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
r1
Relay 1 Form
Relay 1 Form
Normally Open
This section includes selecting the
remote control source for the actuator
along with configuring the local
controls, changing the colour of the
closed LED, changing the display
language and performing a full stroke
reference test.
9.3
General Settings
The correct setting for remote control
source will be determined by the type
of remote control required and the
option specified and fitted, if any.
There are five options available to
configure the remote control source:
[
r
E]
Digital (Default):
Select this option
for hard-wired pushbutton / relay
contact control.
[AI]
Analogue:
Select this option if the
actuator is remotely controlled by an
external analogue signal in the range
0-20 mA or 0-10 Volts, with or without
offset zero.
[OP]
Option:
Select this option if the
actuator is fitted with one of the
following Network cards:
Pakscan
Modbus
Profibus
Foundation Fieldbus
DeviceNet
[OE]
Option ESD
: Select this option
if the actuator is fitted with one of
the Network cards listed above and a
hardwired ESD override facility is also
required.
[OF]
Off
: Select this option to disable
control from a remote source. The
actuator will operate from the local
controls only.
To change the configuration press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Remote Select
Od
Remote Select
Digital