33
Change Language
English
Language
UL
The default display text language is
English. Consult the factory for which
additional display text languages are
available.
To change the language press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Full Stroke Setup (Reference Test)
SF
This function performs a full cycle of the
actuator and records the position and
internal hydraulic pressure against time
in both the open and closed directions.
This should be carried out once the
actuator has been commissioned on
site. Using Insight II it can then be
compared against subsequent tests
carried out at a later date.
The actuator needs to be positioned at
a limit to perform this test.
[SF]
Perform the full stroke reference
test.
PRESS THE
KEY.
F-Stroke Setup
Confirm?
F-Stroke Setup
- No +
This brings up an option to either
cancel or confirm that the reference
partial stroke test should be completed.
To cancel the test: Ensure that
[No]
is
displayed on the screen
PRESS THE
KEY.
To confirm that the test should be
completed: Press the
+
key until the
display changes to
[yS].
PRESS THE
KEY.
F-Stroke Setup
- Yes +
Digital Control
9.4
This section includes selecting the
action for 2-wire priority and settings
related to how the actuator should hold
its current position.