38
Partial Stroke Setup (Reference Test)
SP
P-Stroke Setup
Confirm?
P-Stroke Setup
- No +
This brings up an option to either
cancel or confirm that the reference
partial stroke test should be completed.
To cancel the test: Ensure that
[No]
is
displayed on the screen
PRESS THE
KEY.
To confirm that the test should be
completed: Press the + key until the
display changes to
[Ys]
PRESS THE
KEY.
P-Stroke Setup
- Yes +
This function performs a partial
stroke of the actuator and records
the position and internal hydraulic
pressure against time in both the open
and closed directions. This should be
carried out once the actuator has been
commissioned on site. Using Insight
II it can then be compared against
subsequent tests carried out at a later
date.
The actuator needs to be moved to the
limit that the partial stroke test should
be started from prior to initiating the
test.
[SP]
Perform the reference partial
stroke test.
PRESS THE
KEY.