40
The CPT output can be set to either
represent the position or internal
hydraulic pressure as a current (4 - 20
mA) output.
To change the type of output press the
+ or – key until the required setting is
displayed
[Po] Position (Default):
The CPT will
output the actuators current position.
[Pr]
Pressure:
The CPT will output the
actuators current internal hydraulic
pressure.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
CPT Output
Type
Position
Set CPT Output
Co
To calibrate the CPT output for the
closed limit position, connect a current
measuring device to the CPT terminals.
Press the + or – keys until the required
output is shown on the measuring
device.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Set CPT Output
- < < Closed > > +
CPT – Set Closed
Sc
To calibrate the CPT output for the
open limit position, connect a current
measuring device to the CPT terminals.
Press the + or – keys until the required
output is shown on the measuring
device.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Set CPT Output
- < < Open > > +
CPT – Set Open
SO