54
Setting instructions for actuators
including an optional Profibus DP
module – check wiring diagram for
inclusion.
Before setting the parameters for
Option Profibus ensure Remote
Control Source [Od] has been
selected to [oP] in Section 9.3.
Any settings made locally at
the actuator may be overwritten by
the host on startup unless the GSD
files are locked on the Profibus card.
Refer to publication PUB088-004
available from www.rotork.com
The actuator power must be
cycled for the changes to take effect.
The Profibus DP module must be
allocated a unique address.
To set the address the Profibus module
must be isolated from the host by
disconnecting the RS485 highway or
turning off the host device.
Using the
+
or
-
keys display the
required address.
Address to be set within the range
(01-126 to 7E Hexadecimal)
(refer to
section 12 conversion)
. If an address
value outside this range is entered, the
address set will revert to 01 (for 00) or
7E (for value above 7E).
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Press the
k
to display:
[Pb]
Baud Rate
.
[Pb]
has no relevance for the
Rotork Profibus DP Mk.2 card.
Therefore, if the Rotork Profibus DP Mk.2
card is fitted, press the
k
to display:
[PF]
Aux I/P Mask
.
9.12
Bus System
Option Profibus DP [OP]
PA
Node Address
Hex 01 : Dec 001
Profibus Node
Address