57
Setting instructions for actuators
including an optional DeviceNet DFU
module – check wiring diagram for
inclusion.
Before setting the parameters for
Option DeviceNet ensure Remote
Control Source [Od] has been
selected to [oP] in section 9.3
.
The actuator power must be
cycled for the changes to take effect.
The DeviceNet module must be
allocated a unique address.
Using the
+
or
-
keys display the
required address.
Address to be set within the range (01-
63 to 3F Hexadecimal). See page 79 for
conversion. If an address value outside
this range is entered, the address set
will revert to 01 (for 00) or 3F (for value
above 3F).
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Press the
k
key to display:
[Pb]
Baud Rate
.
The DeviceNet module must be set to
the DeviceNet highway baudrate.
Using the
+
or
-
keys display the
required baudrate:
[01]
= 125 k baud
[03]
= 250 k baud
[06]
= 500 k baud
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Press the
k
key to display:
[PF]
Aux I/P Mask
.
9.13
PA
DeviceNet Baudrate
Pb
Node Address
Hex 01 : Dec 001
Baud Rate
500k baud
DeviceNet Node
Address
Bus System
Option DeviceNet