59
PF
DeviceNet Remote
Auxiliary Input (continued)
Using the
+
or
-
keys display the
required mask setting.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
For DeviceNet module positioning
settings and action on loss of signal
setting
[OF]
.
Refer to section 9.14.
Aux I/P Mask
Bits: 0000 1111
5. Remote I/P Setting
Ensure that the correct
[Od]
Control Type
setting is selected
(refer to section 9.3)
.
For DeviceNet this is
[OP]
Network
.
The factory default for
[PF]
Aux I/P Mask
is
[OF]
0000 1111
.
Examples
1. The full range of remote controls is needed. Open and Close are NO and ESD
and Stop/maintain is NC.
Aux I/P 4 3 2 1
Function
1 1 1 1
= F
Invert
0 0 1 1
= 3 i.e. set [PF] to [F3]
2. Open and close control is required along with 2 inverted digital signal inputs.
(Note that with this setting the open and close commands will be maintained.)
Aux I/P 4 3 2 1
Function
0 0 1 1
= 3
Invert
0 0 1 1
= 3 i.e. set [PF] to [33]
3. Only an ESD input is needed. The requirement is for push to run control with a
NO contact input.
Aux I/P 4 3 2 1
Function
1 1 0 0
= C
Invert
1 0 0 0
= 8 i.e. set [PF] to [C8]