All EH actuator functions are configured to a set of Rotork Fluid Systems default
(standard) settings before despatch, see the table opposite. When requested,
alternative settings specified with the order will be used. When site commissioning
takes place, entered settings overwrite Rotork Fluid Systems defaults and these
‘‘current’’ settings are used for operation along with the remaining unadjusted
defaults.
Should difficulty be encountered during commissioning the default settings can be
reinstated, returning the actuator configuration to its original manufactured state.
Site commissioning must then begin again.
If reset to factory defaults takes place, all Basic and Configuration Settings
except limit positions will return to their default setting. See the table
opposite for Rotork Fluid Systems standard settings.
Basic settings (except
limits) and Configuration settings must then be checked and reset as required
Refer to Basic Settings, section 8 and Configuration Settings, section 9.
Rotork Fluid Systems standard default settings for EH actuators:
Function
[d1] Default Setting
[P?]
Password
Unaffected – will remain as set
[Bt]
Bluetooth
Communication
[OF]
Switched Off
Basic Configurations
[C2]
Close Action
[CP]
Stop on Pressure
[C3]
Open Action
[OL]
Stop on Limit
[CP]
Close Pressure at Limit
[90]
90% of Maximum Pressure
[Cp]
Close Pressure at Mid
[00]
00% = Value set in CP
[OP]
Open Pressure at Limit
[90]
90% of Maximum Pressure
[Op]
Open Pressure at Mid
[00]
00% = Value set in OP
Configuration Settings
[r1]
Relay 1 Function
[CL]
Closed Limit
[r1]
Relay 1 Form
[nO]
Normally Open
[Od]
Remote Select
[rE]
Digital
[cL]
Local Control
[Pr]
Push to Run
[LP]
Low Power Mode
[OF]
Switched Off
[Ld]
Closed LED Colour
[9r]
Green
[UL]
Language
[01]
English
[rP]
Remote Priority
[SP]
Stayput
[HP]
Hold Position
[On]
Switched On
[PH]
Position Hysteresis
[05]
0.5%
[OH]
Over Pressure Hysteresis
[10]
10%
[UH]
Under Pressure Hysteresis
[10]
10%
[EA]
ESD Action (Software)
[ E]
De-energise all
Solenoid
Valves
[EO]
ESD Local Stop Override
[No]
No Override
[Ec]
ESD Contact Type
[nO]
Normally Open
[rE]
ESD Manual Reset
[OF]
No Reset
[Et]
ESD Temp Loss of Signal
[Ct]
Continue with ESD Action
[PP]
Partial Stroke Position
[90]
90% Open
[Ph]
Partial Stroke Test
[No]
Do not start motor when
– Motor Start
test commences
[FI]
mA / Voltage Analogue Input
[CU]
Current
Ur
Reset to Default