A4
US
US
A4
US
A4
US
A4
A4
US
US
A4
US
A4
A4
US
IQ3 Full Configuration Manual – Section: Settings
19
1/20
Control Source 1
Control Source 1 will be set by Rotork for the fitted remote
Analogue or Network control option(s). Refer to Table: Control
Source Settings.
2/20
Control Source 2
Control Source 2 will be set by Rotork for the fitted remote
Analogue or Network control option(s). Refer to Table: Control
Source Settings.
3/20
Ctrl Selection
Control Selection is used to select the control source and if
required, for Analogue option or Analogue with Network
options, allow hardwired switching between sources using the
Manual/Auto input.
Disabled
– All remote control disabled. The actuator can only be
operated using the local controls.
Hardwired
– Remote control by hardwired inputs only. This
setting is the default for actuators with no option cards fitted.
If a Network option is fitted but is not required for
control, to select Hardwired.
Source1
– Control by the option listed for Control Source 1.
If Control Source 1 is a Network option, control will be via its
auxiliary mask inputs, refer to 2.3.2-5.
Hardwired / Source1
– Control available only when Analogue
option is fitted. This mode enables the user to select between
control by hardwired inputs or source 1 (Analogue) control by
applying or removing a signal to the Manual/Auto input, refer to
wiring diagram. Manual will enable hardwired control and Auto
will enable Source1 control.
If an Analogue option is fitted and Manual/Auto switching
is required, to select Hardwired/Source 1.
Source 1 (Ang) / Source 2
– Control by Analogue and a
Network option only. This mode enables the user to select
between Source 1 (Analogue) and Source 2 (Network) control, by
applying or removing a signal to the Manual/Auto input available
with the Analogue option, refer to wiring diagram. Manual will
enable source 2 and Auto will enable source 1, refer to 2.3.2-6.
Source 1 / Source 2
– For future use with two Network control
options.
If Analogue and Network options are fitted and Manual/
Auto switching is required, to select Source 1
(Ang) / Source 2.
4/19 to 7/19
Options Fitted
Not editable. Factory set for the control options fitted. Up to 4
options can be fitted and will be indicated in the list. Unused
allocations will be set to Disabled.
If a control option is fitted after manufacture, the allocation will
be set to the fitted option type by Rotork Service. Where the
user upgrades an actuator to include a new control option using
a kit supplied by Rotork, this must be set before the control
mode settings can be made. Contact Rotork for access.
8/20 to 19/20
Lost Signal
Sets the actuator response for when the analogue signal
or Network communications of the control source
are lost.
There are 3 settings for determining the actuator response on
loss of signal and these are common for all option types fitted.
Each group of 3 will be headed with the applicable option type
- example Analogue. For actuators including one control option,
settings 8/20 to 10/20 will be available and settings 11/20 to
20/20 will be greyed out. For 2 options fitted, 8/20 to 13/20
will be available and so on up to 4 options. This instruction is
therefore common for as many options as are fitted.
8/19
Lost Signal Time
Sets the amount of time in seconds that a signal must be lost
before the set lost signal action is performed. Range 0 to 65
seconds:
For the analogue option, time must be set to 0 seconds.
To change, . The time set after which the lost
signal action will be implemented and indicated.
9/19
Lost Signal Action
Sets the action performed when the signal is lost:
Off (default)
– The lost signal feature is disabled. An actuator
with Analogue control will run to the set low signal position. An
actuator with Network Control will stay at its current position
when communication is lost.
Stayput
– If the actuator is not moving it will Stayput, if it is
moving it will Stop.
Close
– The actuator will run to the Close Limit.
Open
– The actuator will run to the Open Limit.
Position
– The actuator will run to the mid-travel position set for
Signal Loss Position, refer to 10/19.
To change, . The drop down list will close and
the selected action will be indicated.
10/19 Lost Signal Position
When the lost signal action is set to Position the actuator will
run to the mid-travel position set. Range is 0% (Closed Limit) to
100% (Open Limit). This control should be used if a lost signal
position in mid-travel is required.
Whenever the actuator is running under positioning mode, the
parameters in the Positioning menu will apply. Refer to 2.3.2-4.
To change, . The slider control will indicate the
mid-travel position the actuator will move to when the
control/network signal is lost.
2.3.2-2 Control – Remote – Control Source
continued
Summary of Contents for IQ Multi-Turn
Page 2: ...2...