38
IQ3 Full Configuration Manual – Section: Status
3.1.2 Control – Remote Hardwired
Control
Local
Remote Hardwired
Remote Source 1
Remote Source 2
Remote Hardwired
Open
Close
ESD
Maintained
Open Interlock
Close Interlock
1/6
Remote Hardwired Status
This screen displays the signal statuses from the remote hardwired
controls. As the remote hardwired controls are operated, the
corresponding signals are produced. The checkbox indicates a
signal is being received, which is useful in testing the operation
of the remote control signals. Valve movement may occur during
testing. If this is not desirable, select STOP on the local controls.
To scroll through this information use
.
1/6
Open
Displays the current Remote Hardwired Open signal status. When
active, this indicates that an open signal is being received from
the remote hardwired control.
2/6
Close
Displays the current Remote Hardwired Close signal status. When
active, this indicates that a close signal is being received from the
remote hardwired control.
3/6
ESD
Displays the current Remote Hardwired ESD signal status. When
active, this indicates that an ESD (Emergency Shut Down) signal is
being applied from the remote hardwired control.
ESD can be set to open, close or stayput. ESD signals are higher
priority than local or remote signals and will operate under both
local and remote control selection. ESD can also be set to operate
an actuator selected to Local Stop. Refer to 2.4.
4/6
Maintained
Displays the current Remote Hardwired Maintained signal status.
When active, this indicates that a maintained signal is being
received from the remote hardwired control.
If a signal is present the actuator will self-maintain as a response
to a fleeting open or close control signal and will run until the
maintain line is broken, it reaches a limit or is reversed.
5/6
Open Interlock
Displays the current Remote Hardwired Open Interlock signal
status. When active, this indicates that an open interlock signal is
being received from the remote hardwired control.
The actuator will not run in the open direction until a signal
is applied to the open interlock and a remote hardwired open
control signal is received.
6/6
Close Interlock
Displays the current Remote Hardwired Close Interlock signal
status. When active, this indicates that a close interlock signal is
being received from the remote hardwired control.
The actuator will not run in the close direction until a signal
is applied to the close interlock and a remote hardwired close
control signal is received.