A4
US
US
A4
US
A4
US
A4
A4
US
US
A4
US
A4
A4
US
IQ3 Full Configuration Manual – Section: Status
39
3.1.3 Control – Remote Source 1
Control
Local
Remote Hardwired
Remote Source 1
Remote Source 2
Remote Source 1
Open
Close
Stopped
ESD
Remote Source 1 Status
This screen displays the signal statuses from remote source 1;
refer to 2.3.2-2 for details of the Source 1 control. The checkbox
indicates a signal is being received.
Note: only digital remote control options are able to
report a control status. For Analogue control, please use
the Positioner home screen to view demand and position
values. Refer to 2.2.2.
To scroll through this information use
.
1/4
Open
Displays the current Remote Source 1 Open signal status. When
active, this indicates that an open signal is being received from
remote source 1.
2/4
Close
Displays the current Remote Source 1 Close signal status. When
active, this indicates that a close signal is being received from
remote source 1.
3/4
Stopped
Displays the current Remote Source 1 Stopped signal status.
When active, this indicates that remote source 1 has been set to
stop.
4/4
ESD
Displays the current Remote Source 1 ESD signal status. When
active, this indicates that an ESD (Emergency Shut Down) signal is
being received from remote source 1.
ESD can be set to open, close or stayput. ESD signals are higher
priority than local or remote signals and will operate under both
local and remote control selection. ESD can also be set to operate
an actuator selected to Local Stop. Refer to 2.4.
3.1.4 Control – Remote Source 2
Control
Local
Remote Hardwired
Remote Source 1
Remote Source 2
Remote Source 2
Open
Close
Stopped
ESD
Remote Source 2 Status
This screen displays the signal statuses from remote source 2;
refer to 2.3.2-2 for details of the Source 2 control. The checkbox
indicates a signal is being received.
To scroll through this information use
.
1/4
Open
Displays the current Remote Source 2 Open signal status. When
active, this indicates that an open signal is being received from
remote source 2.
2/4
Close
Displays the current Remote Source 2 Close signal status. When
active, this indicates that a close signal is being received from
remote source 2.
3/4
Stopped
Displays the current Remote Source 2 Stopped signal status.
When active, this indicates that remote source 2 is set to stop.
4/4
ESD
Displays the current Remote Source 2 ESD signal status. When
active, this indicates that an ESD (Emergency Shut Down) signal is
being received from remote source 2.
ESD can be set to open, close or stayput. ESD signals are higher
priority than local or remote signals and will operate under both
local and remote control selection. ESD can also be set to operate
an actuator selected to Local Stop. Refer to 2.4.
Summary of Contents for IQ Multi-Turn
Page 2: ...2...