A4
US
US
A4
US
A4
US
A4
A4
US
US
A4
US
A4
A4
US
IQ3 Full Configuration Manual – Section: Status
43
3.5 Status – Diagnostics
Status
Control
Alarms
Movement
Indication
Diagnostics
Diagnostics
Mains Fail
Phase Loss
Position Sensor
Hardware Option
Torque Sensor
Network Alarm
Config Error
MEM Missing
1/8
Diagnostics status
This screen displays the actuators diagnostics status. The checkbox
indicates that the fault is present.
To scroll through this information use
.
1/8
Mains Fail
Displays the power supply failure status. When active, this status
indicates a power supply failure has occurred. If the backlight is
still present it is likely that the third phase has been lost. Check all
incoming phases.
2/8
Phase Loss
Displays the Phase Loss status. When active, this status indicates
that one or more phases have been lost. Only the third phase
is monitored so if the backlight is present then check the third
phase is present. If the backlight is not present, check all phases.
3/8
Position Sensor
Displays the absolute encoder fault status. When active, this
status indicates that a fault with the absolute encoder has
occurred. Check the encoder operation and loom.
4/8
Hardware Option
Displays the communication fault status between the main control
board and the option board. When active, this status indicates
that a communication error has occurred. Check all connections
between the option PCB and the main controller PCB.
5/8
Torque Sensor
Displays the fault status of the Torque Sensor. When active, this
status indicates that a fault has occurred with the torque sensor.
Check the torque sensor and loom.
6/8
Network Alarm
Displays the network fault status. When active, this status
indicates that a fault has occurred in the network. Check all field
connections for continuity and correct connection.
7/8
Config Error
Displays the EEPROM fault status. When active, this status
indicates that a fault with the EEPROM has occurred. Check all
configuration settings.
8/8
MEM Missing
Displays the EEPROM missing status. When active, this status
indicates that the EEPROM is missing. The EEEPROM stores all the
actuators settings and calibration. If the EEEPROM is physically
missing, please contact Rotork for further advice.
Summary of Contents for IQ Multi-Turn
Page 2: ...2...