66
IQ3 Full Configuration Manual – Section: Assets
Open Torque
1/10 Hi Alarm %
- Allows the user to set a value for an open
torque alarm. E.g. 70%.
2/10 HiHi Alarm %
- Allows the user to set a value for a second
open torque alarm. E.g. 75%.
Close Torque
3/10 Hi Alarm %
- Allows the user to set a value for a close
torque alarm. E.g. 70%.
4/10 HiHi Alarm %
- Allows the user to set a value for a second
close torque alarm. E.g. 75%.
Misc Trip Levels
5/10 Max Starts/Hr
– Allows the user to set a value for the max
starts per hour alarm. E.g. 50 starts.
6/10 Total Starts
– Allows the user to set a value for the total
starts alarm. E.g. 5000 starts.
7/10 Total Turns
– Allows the user to set a value for the total
turns alarm. E.g 15,000 turns.
8/10 Vibration
– If the vibration level, which is set by the
customer, is reached the alarm will trigger. It can be set between
1000mG and 8000mG.
Service
9/10 Interval (Months)
– Allows the user to set an alarm for
the next service due. Displays number of months between each
service.
Alarms
10/10 Clear Active Alarms
– Clears all active alarms.
5.6 Assets – NAMUR 107
Close Limit
NAMUR Level
MAN
OOS FNC
FAI
Battery Low
Local Ctrl Fault
Mains Fail
Thermostat
Serv. Contactor
Service Due
Hi Hi Torq. Alarm
1/24
NAMUR 107 Settings
This screen allows the user to view alarms for NAMUR 107
recommendations and set these alarms once a valid password
has been entered. The NAMUR 107 diagnostics framework splits
actuator condition statuses into four groups. This is based on the
outcome severity of an active condition or the type of condition
shown. The four settings available for NAMUR 107 diagnostics
are:
NAMUR Allocation
Description
Alarm
MAN
Maintenance required
N107 Maintenance
OOS
Out of specification
N107 Out of Specification
FNC
Function check
N107 Function Check
FAI
Failure
N107 Failure
NAMUR 107 alarms are meant for indication only and will alert
the user to potential operational issues with the actuator/valve.
Alarms can be set to activate when a selected condition has
occurred. For remote monitoring, an output relay can be set to
indicate an N107 alarm type is active, refer to 2.2.1. The NAMUR
107 system enables multiple actuator conditions to be monitored
through one relay output remotely. This will initiate further
investigation into the root cause of the problem.
Typical uses
For example, a process controller requires detailed N107
diagnostics to integrate a new process into an existing NAMUR
107 system. Particular actuator conditions will be monitored
and assigned to user specified N107 alarms for monitoring. Each
N107 alarm can be allocated to a relay output to provide remote
diagnostics for various actuator conditions, refer to 2.2.1.
The Battery Low, Service Due and Hi Torque Alarm conditions are
assigned to the N107 Maintenance category. Should one of these
conditions become active, an output relay, correctly configured
for the N107 Maintenance alarm, will indicate a maintenance
issue. The operator will then be able to check the status of the
actuator to determine which of the three allocated conditions are
active and find the appropriate solution.
Other conditions can be configured to the remaining NAMUR
107 categories and integrated into the system appropriately.
To edit information use and to highlight the
required field.
To change, press
to select /deselect the field.
5.5 Assets – Service Alarms
continued