IQT3 manual – Section: Commissioning - Basic Settings
8. Commissioning - Basic
Settings
All actuator settings, Data logger and
asset management data is accessed
using the supplied Rotork
Bluetooth
®
Setting Tool Pro. Status and alarm data
in addition to that shown on the home
screen can also be accessed.
THE CONTROL COVER MUST
NOT BE REMOVED; NO USER
CONFIGURABLE SETTINGS ARE
AVAILABLE WITHIN THE CONTROL
ENCLOSURE. THE CONTROL
COVER IS SEALED BY A QUALITY
LABEL WHICH IF BROKEN MAY
INVALIDATE WARRANTY.
This instruction details the basic
settings that must be completed before
the actuator is put into service.
ELECTRICAL OPERATION MUST
NOT TAKE PLACE UNTIL THE BASIC
SETTINGS HAVE BEEN MADE AND
CHECKED.
The basic settings affect the correct
operation of the valve by the actuator.
If the actuator has been supplied with
the valve, the valvemaker or supplier
may have already made these settings.
Settings and operation must be
verified by electric operation and
function test of the actuated valve.
THIS PUBLICATION PROVIDES
INSTRUCTION ON MAKING THE
BASIC SETTINGS ONLY.
For instruction on control and
indication settings and for information
on diagnostics refer to PUB002-040.