IQT3 manual – Section: Commissioning - Basic Settings
19
Use the or arrow keys to change
the setting to the required value, the
example below show a close action of
Torque
having been selected.
Stopped
Close
Settings
Direction
Clock
Anti
Action
Limit
Torque
Torque
100%
Set Limit
Open
Settings
Action
Limit
Torque
Torque
60%
2/15
LED INDICATION: R = RED, G = GREEN, Y = YELLOW, B = BLUE
Y
Y
Fig. 8.2.5
Press the
key to select.
The highlight will return to the function
name only and its stored setting will be
displayed:
Stopped
Close
Settings
Direction
Clock
Anti
Action
Limit
Torque
Torque
100%
Set Limit
Open
Settings
Action
Limit
Torque
Torque
60%
2/15
LED INDICATION: R = RED, G = GREEN, Y = YELLOW, B = BLUE
Y
Y
Fig. 8.2.6
The password will be requested
the first time a function is selected.
Once correctly entered, the
password will not be required to
be entered again for the duration
of setting tool communication with
the actuator. Other functions can
be set as required.
8.3 Basic Settings Menu
Settings Menu
Limits
Indication
Control
ESD
Security
Defaults
CLOSE SETTINGS
Direction (CW/ACW)
Action (Torque/Limit)
Torque (40 - 100%)
Set Limit
OPEN SETTINGS
Action (Torque/Limit)
Torque (40 - 100%)
Set Limit
Turns
Position
Speed
TORQUE SWITCH
BYPASS
Open
Open Position (0 - 95%
Close
Closing Position (100 - 5%)
AUTO LIMIT SETTING