IQT3 manual – Section: Commissioning - Basic Settings
8.4 Basic Settings – Limits
Settings and operation must be
verified by electric operation and
function test of the actuated valve.
Connect to the actuator as described in
Section 8.1. From the Position display
home screen press the
key. The
main menu will be displayed.
Navigate to Settings using the
keys and press
to select.
Fig. 8.4.1
The settings menu will be displayed:
Settings
Limits
Indication
Control
ESD
Security
Defaults
Navigate to Limits using the keys
and press
to select.
The setting first selected to be
changed will require a password to
be entered – refer to section 8.2.
The limit settings are shown below
with their factory default values:
Limits
Close Settings
1 / 15
Direction
Clock
Anti
2 / 15
Action
Limit
Torque
3 / 15
Torque
40%
4 / 15
Set Limit
Open Settings
5 / 15
Action
Limit
Torque
6 / 15
Torque
40%
7 / 15
Set Limit
8 / 15
Turns
25
9 / 15
Position
95.0
10 / 15
Speed
40%
Torque Switch Bypass
11 / 15
Opening
On
X
Off
12 / 15
OP. Bypass Pos
10%
13 / 15
Closing
On
X
Off
14 / 15
CL. Bypass Pos
90%
Auto Limit Setting
15 / 15
Auto Set Limit
1 / 15
Function Close Direction (1 / 15) is shown highlighted. Use
to scroll through
functions. Functions will be highlighted in turn.