Modbus MFU Option Card Installation Manual
48 of 76
Publication PUB091-003-00_0119
7.6.3
Data Accessed with Function Code 03 - Read Holding Registers
The accessible registers that can be read with this function code also include the Input registers.
Location
(Reg/Bit)
R/W
Data
Range
0
0
RO
Actuator moving
0-1
0
1
RO
Closed limit
0-1
0
2
RO
Open limit
0-1
0
3
RO
Running closed
0-1
0
4
RO
Running open
0-1
0
5
RO
Remote selected
0-1
0
6
RO
Local Stop selected
0-1
0
7
RO
Local selected
0-1
0
8
RO
Thermostat tripped
0-1
0
9
RO
Monitor relay
0-1
0
10
RO
Valve obstructed
0-1
0
11
RO
Valve jammed
0-1
0
12
RO
Valve moving by hand
0-1
0
13
RO
Moving inhibited
0-1
0
14
RO
Position control enabled
0-1
0
15
RO
Watchdog recovery
0-1
1
0
RO
Battery low
0-1
1
1
RO
Open interlock active
0-1
1
2
RO
Close interlock active
0-1
1
3
RO
DI-1
0-1
1
4
RO
DI-2
0-1
1
5
RO
DI-3
0-1
1
6
RO
DI-4
0-1
1
7
RO
Slow mode
0-1
1
8
RO
Reserved
0
1
9
RO
Reserved
0
1
10
RO
Reserved
0
1
11
RO
Reserved
0
1
12
RO
Reserved
0
1
13
RO
Reserved
0
1
14
RO
Reserved
0
1
15
RO
Reserved
0
2
-
RO
Actuator Instantaneous Torque
①
0-78 hex
(0 –120%)
3
-
RO
Valve Position
0-3E8 hex
(0.0 – 100.0%)
4
-
RO
Analogue Input
0-3E8 hex
(0.0 – 100.0%)