Modbus MFU Option Card Installation Manual
70 of 76
Publication PUB091-003-00_0119
12.2.2 Digital Input Status Feedback
Status Feedback
IQ
IQT
Definition
Actuator Moving
Centre column moving for any reason
Close Limit
End of travel position, closed position achieved
Open Limit
End of travel position, open position achieved
Thermostat Tripped
Motor temperature thermostat operated
Monitor Relay
Local or Local stop selected or Phase loss or
thermostat tripped
Local selected
Selector in local control position
Remote selected
Selector in remote control position
Battery Low
Battery power low
Running Closed
Actuator close contactor energised
Running Open
Actuator open contactor energised
Interrupter Timer
Interrupter Timer operating
MIT Active
Motion Inhibit Timer active
Open Interlock input
Open Interlock present
Close Interlock input
Close Interlock present
Position Control Enabled
Actuator in positioning mode
Error
Device Fault, use Loopback Test to determine the
error.
S1
Setting for S1 on the actuator
S2
Setting for S2 on the actuator
S3
Setting for S3 on the actuator
S4
Setting for S4 on the actuator
DI –3
Remote input for Stop condition
DI –2
Remote input for Close condition
DI –1
Remote input for Open condition
DI –4
Remote input for ESD condition
Note:
– The ‘S’ contacts are no longer monitored by the hardware
12.2.3 Analogue Input Status Feedback
Analogue Feedback
IQ
IQT
Definition
Actuator Instantaneous
Torque
Current torque value,
Scale: 0-120% = 0-65536
Valve Position
Current position,
Scale: 0-100% = 0-65536