Input and Output Signals
Publication PUB088-005-00_1017
41 of 84
F
ou
nd
ati
on
F
iel
db
us
FF
-01
In
s
tal
lat
io
n m
an
u
al
5.2 Digital Input Status Feedback
The Profibus DP Module (Mk2) cyclically reports over the network a comprehensive data set relating
to the status of the valve, actuator and card settings as indicated in the table below.
Register Name
Status Feedback
IQ IQT
Q CVA
EH/
Skil
ROM
PAK
IDATA1/0
Register 0 Bit 0
Actuator Moving
IDATA1/1
Register 0 Bit 1
Close Limit
IDATA1/2
Register 0 Bit 2
Open Limit
IDATA1/3
Register 0 Bit 3
Running Closed
IDATA1/4
Register 0 Bit 4
Running Open
IDATA1/5
Register 0 Bit 5
Remote selected
IDATA1/6
Register 0 Bit 6
Local Stop selected
IDATA1/7
Register 0 Bit 7
Local selected
IDATA2/0
Register 0 Bit 8
Thermostat Tripped
⑥
IDATA2/1
Register 0 Bit 9
Monitor Relay
IDATA2/2
Register 0 Bit 10
Valve Obstructed
IDATA2/3
Register 0 Bit 11
Valve Jammed
IDATA2/4
Register 0 Bit 12
Valve Moving by Hand
IDATA2/5
Register 0 Bit 13
Moving Inhibited
IDATA2/6
Register 0 Bit 14
Position Control Enabled
IDATA2/7
Register 0 Bit 15
Watchdog Recovery
IDATA3/0
Register 1 Bit 0
Battery Low
IDATA3/1
Register 1 Bit 1
Open Interlock input
IDATA3/2
Register 1 Bit 2
Close Interlock input
IDATA3/3
Register 1 Bit 3
DI
–1
IDATA3/4
Register 1 Bit 4
DI
–2
IDATA3/5
Register 1 Bit 5
DI
–3
IDATA3/6
Register 1 Bit 6
DI
–4
IDATA3/7
Register 1 Bit 7
Slow Mode
IDATA4/0
Register 1 Bit 8
GSD Configuration Permitted
IDATA4/1
Register 1 Bit 9
Reserved
IDATA4/2
Register 1 Bit 10
Control Contention
IDATA4/3
Register 1 Bit 11
Partial Stroke in Progress
IDATA4/4
Register 1 Bit 12
Part Stroke Error
IDATA4/5
Register 1 Bit 13
Primary (0) or Back up (1)
IDATA4/6
Register 1 Bit 14
1 or 2 Channels Available
IDATA4/7
Register 1 Bit 15
SR (0) or FR (1) mode
Note:
– This bit is reported when within the slow mode band, but does not affect the actuator
- This bit represents the Fault Relay Output on EH / Skil
- This bit indicates the state of the Hardwired Partial stroke input on EH / Skil
- Test mode, refer to CVA actuator information
- Dual channel option not available for CVA
⑥
- Thermostat is tripped when CVA is set to hand operation