Profibus DP Mk2 Option Card Installation Manual
60 of 84
Publication PUB088-005-00_1017
Param.
No.
Description
Value/Range
Default Value
9
Watchdog Timeout
0
– 255 sec
0000
– 00FF hex
10 sec
000A hex
10
Action on Loss of Comms
0 = Nothing (No Action)
1 = Open
3 = Close
5 = Stop
7 = Position
Any other value = Off
0 = Nothing
(0000 hex)
11
Comms Lost Position
0
– 100%
0000
– 0064 hex
0%
0000 hex
12
Comms Fault Timer
0
– 255 sec
0000
– 00FF hex
255 sec
00FF hex
13
Aux Input Mask
0
– 255
0000
– 00FF hex
15
000F hex
14
ESD DI4/Net Disable
and Data logger disable
DI-4 is ESD = 0 or 2
DI-4 is Net Disable = 1 or 3
Data Logger is enabled = 0 or 1
Data Logger is disabled = 2 or 4
(Bit 0 = EDS/Net disable
Bit 1 = data logger en/disable)
ESD and
Data Logger
enabled
0
0000 hex
15
Redundancy FR/SR mode
and Simple/RedCom mode
Bit 0 : SR mode = 0, FR mode = 1
Bit 1 : Simple = 0, RedCom = 1
0
0000 hex
16
Part Stroke position
1
– 99%
0001
– 0063 hex
90
005A hex
17
Part Stroke Limit and timeout
Bit 15 is 0 for close limit and 1 for open
limit.
Bits 0-14 are time values in seconds for
timeout
Open and
300 secs
812C hex
18
Actuator Type
0
–Don’t know (default), 2–A/AQ/Q,
6
–IQ, 8–IQT, 9–EH, 10–Skilmatic,
11
–Multiport, 12-CVAL, 13-CVAQ,
14- ROMPAK
0
19
Reserved
0
0
Note:
- Setting the
deadband lower than the hysteresis, or the hysteresis greater than the
deadband causes the hysteresis to be set to 0.1%
-
IQ Setting tool only allows 0.0 to 9.9% deadband to be set
- On Redcom Dual Channel cards the default is 2 (0002 hex)
These parameters set up the response the actuator will make to various control and network actions.
There are three GSD files, one for a single channel card, one for a simple dual channel and one for a
RedCom dual channel card. They all contain the same number of parameter settings.
Single Channel Card
GSD file
RTRK0845
Simple Dual Channel Card
GSD file
RTRC0845
RedCom Dual Channel Card GSD file
RTRR0845