Setting Up a Card
Publication PUB088-005-00_1017
81 of 84
P
a
k
s
c
a
n Mo
dbus
Dat
a
Ba
s
e
I
nf
orma
tion
8.3 Setting up a Skil or EH with the Infra-red Setting Tool
The Skil and EH actuator includes an infra-red communication port for setting the actuator
performance, limit switches and so on. This communication link is also used to select the remote
source for the actuator.
The choices for remote source are as follows:
[OF]
– No remote control from any source.
[rE]
– Remote control from Remote Digital Inputs
ONLY
.
[OP]
– Remote control from an Option card, control from remote Digital Inputs possible if
the Auxiliary mask set correctly.
[OE]
- Remote control from an Option card, control from remote Digital Inputs possible if
Auxiliary mask set correctly.
BUT
the ESD input is Hardwired i.e. the Auxiliary mask
does not apply to this particular input and the ESD will operate as if the setting were
[rE]
.
Fig 42: Skil and EH setting tool menu structure showing remote select
Refer to the installation manual of the actuator for more details.
8.3 Maintenance and Repair
There is no periodic service requirement for the PFU.
Repairs should not be attempted on the module. The Network Interface Card and Interface Card are a
pair and should never be separated. Replacing the complete PFU assembly with a new replacement
device should rectify any failure. Static sensitive devices are used in the PFU, it is therefore mandatory
to observe anti-static precautions when handling or working on the unit.