- 5 -
www.rotork.com www.remotecontrol.se
Set up and Order
CONTROL / WARNING LAMP
Power On
Main Power Input
Power On / Off Flickering
CH1, CH2 in case of optional setting
Fault On / Off Flickering
Input defect/disconnection
Close On Lighting
Full Close
Open On Lighting
Full Open
Fault On Lighting&
Close On / Off Flickering
Potentiometer disconnection
Fault On Lighting &
Open On / Off Flickering
Potentiometer P1,
P3 Inverse Disconnection
Fault On Lighting&
Close On Lighting
When manual control of the hande exceeds the close limit setting
Fault On Lighting&
Open On Lighting
When manual control of the hande exceeds the open limit setting
ACTUATOR manually using the lever on the handle and you will FULL CLOSE.
(Refer to page 6)
1
ACTUATOR
FULL CLOSE
Set the CLOSE LIMIT SWITCH ACTUATOR.
(Refer to page 6)
2
CLOSE
LIMIT SETTING
When the ACTUATOR FULL CLOSE status, POTENTIOMETER to determine the value.
*
The factory is set to 80 ~ 120Ω. If you have not been set 80 ~ 120Ω, please reset.
(Refer to page 6)
3
POTENTIOMETER
CHECK
Using the manual lever or handle to the FULL OPEN ACTUATOR then, in the same way
to set the OPEN LIMIT SWITCH.
(Refer to page 6)
4
ACTUATOR
FULL OPEN
&
OPEN LIMIT SETTING
Caution!
1. Confirm that the wiring diagram located in the ACTUATOR and Wiring No. on the
nameplate match with each other.
2. INPUT and OUTPUT of the +, - if the substrate is changed, so Please be sure to
break.
(Refer to page 7)
5
Electric Wiring and
Power Input
Please make sure to press the autoscan button for at least 2 seconds before operating
proportional control.
ACTUATOR automatically CLOSE, OPEN, while the behavior is to automatically check
for abnormalities.
(Refer to page 8)
6
AUTO SCAN
After entering the 4-20mA INPUT, ACTUATOR make sure that the normal operation.
Determine when the problem occurred after the warning lamp to reset the settings of its
contents.
(Refer to page 8)
7
4-20mA
INPUT
4-20mA OUTPUT not fit, the volume is set using switches..
(Refer to page 8)
8
4-20mA
OUTPUT