Electrical characteristics limit switch
min.
typ.
max.
unit
After one-off operation
with U > 24
VAC/DC or I > 100
mA:
• U
min
AC/DC*
• I
min
AC/DC*
12
100
V
mA
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP66
Operation
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
Storage
• Ambient temperature
–40
+70
°C
*: Nominal value: please note that nominal values are also subject to tolerances. For more
detailed information, see:
3.10.18 Max-15-BF, Max-15-BF-CTS, Max-15-BF-VAS
Mechanical characteristics
min.
typ.
max.
unit
Motor torque*
15
Nm
Motor run time for 90° (can be configured with rotary switch)*
3
15
30
60
120
s
Spring torque*
15
Nm
Spring return time for 90° (can be configured with rotary
switch)*
3 / 10
s
Minimum angle of rotation*
-5
°
Maximum angle of rotation*
90
°
Weight*
• Max-15-BF
• Max-15-BF-CTS
• Max-15-BF-VAS
3.8
3.8
5.6
kg
kg
kg
3 | Device description
100