Environmental conditions
min.
typ.
max.
unit
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
Storage
• Ambient temperature
-40
+70
°C
*: Nominal value: please note that nominal values are also subject to tolerances. For more
detailed information, see:
3.10.31 Max-30-F, Max-30-F-CTM
Mechanical characteristics
min.
typ.
max.
unit
Motor torque*
30
Nm
Motor run time for 90° (can be configured with rotary switch)*
40
60
90
120
150
s
Spring torque*
30
Nm
Spring return period for 90°*
20
s
Minimum angle of rotation*
-5
°
Maximum angle of rotation*
90
°
Weight*
• Max-30-F
• Max-30-F-CTM
9.5
9.5
kg
kg
Dimensions
min.
typ.
max.
unit
Max-30-F
L
W
H
–1
–1
–1
288
149
116
+1
+1
+1
mm
mm
mm
Max-30-F-CTM
L
W
H
–1
–1
–1
288
149
116
+1
+1
+1
mm
mm
mm
Hollow shaft double square
16
×
16
mm
Allen key provided for manual adjustment in accordance with
these instructions*
4
mm
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27
131