3.5
Special versions
Label. Properties
S1
• Drive unit without anti-backdrive mechanism (drive can be turned back by external load
when the power is switched off).
• Cable length 1.5 m
S2
• No thermal cutoff (only available as
InMax
)
S3
• To +60
°C
Restrictions
– for
ExMax
and
RedMax
: Temperature class T4
– only suitable for
110
V ... 240
V
– maximum
25 % duty cycle
– cannot be supplied for Y drives
S7
• Only for InMax
• Drive unit without anti-backdrive mechanism (drive can be turned back by external load
when the power is switched off).
• Max-S with aluminium housing with additional damping elements, maximum load 500
g
S9
• No thermal cutoff (only available as
InMax
)
• Limit switch configured to 0/80° instead of 5/85°
S12
• Drive unit without anti-backdrive mechanism (drive can be turned back by external load
when the power is switched off).
S14
• To +60
°C
Restrictions
– for
ExMax
and
RedMax
: Temperature class T4
– only suitable for
110
V ... 240
V
– cannot be supplied for Y drives
S17
• Cable length 3.0
m
S18
• Drive unit without anti-backdrive mechanism (drive can be turned back by external load
when the power is switched off).
• Angle of rotation limited to 90
° by the drive itself
S27
• To +60
°C
Restrictions
– for
ExMax
and
RedMax
: Temperature class T4
– only suitable for
110
V ... 240
V
– maximum
25 % duty cycle
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27
15