Electrical connection options
Cable type 5+PE, cable diameter 7.5
mm
1-wire with spring return with con-
figurable spring return period [p.26]
3-point with spring return with con-
figurable spring return period [p.26]
1-wire with spring return continu-
Without spring return continuous
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP66
Operation
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
Storage
• Ambient temperature
–40
+70
°C
*: Nominal value: please note that nominal values are also subject to tolerances. For more
detailed information, see:
3.10.6
Max-5.10-SF, Max-5.10-SF-CTS, Max-5.10-SF-VAS
Mechanical characteristics
min.
typ.
max.
unit
Motor torque (can be configured with rotary switch)*
5 / 10
Nm
Motor run time for 90° (can be configured with rotary switch)*
3
15
30
60
120
s
Spring torque*
10
Nm
Spring return time for 90° (can be configured with wire bridge
on connection)*
3 / 10
s
Minimum angle of rotation*
-5
°
Maximum angle of rotation*
90
°
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27