Electrical characteristics limit switch
min.
typ.
max.
unit
Signal operation
• U
max
DC*
• I
max
DC*
• I
min
AC/DC*
48
1
5
V
A
mA
Power operation
• U
max
AC*
• U
min
AC/DC*
• I
max
AC*
250
5
5
V
V
A
After one-off operation
with U > 24
VAC/DC or I > 100
mA:
• U
min
AC/DC*
• I
min
AC/DC*
12
100
V
mA
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP66
Operation
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
Storage
• Ambient temperature
–40
+70
°C
*: Nominal value: please note that nominal values are also subject to tolerances. For more
detailed information, see:
3.10.15 Max-15-SF1, Max-15-SF1-CTS, Max-15-SF1-VAS
Mechanical characteristics
min.
typ.
max.
unit
Motor torque*
15
Nm
Motor run time for 90° (can be configured with rotary switch)*
3
15
30
60
120
s
Spring torque*
12
Nm
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27
91