SI manual – Section: Basic Settings for Commissioning
21
7. Basic Settings for
Commissioning
All actuator settings, data logger and
asset management data is accessed
using the supplied Rotork Bluetooth
®
Setting Tool
Pro
(BTST). Status and
alarm data in addition to that shown
on the home screen can also be
accessed.
WARNING:
The electronics
cover must not be removed; no user
configurable settings are available
within the electronics enclosure. The
electronics cover is sealed by a quality
label which if broken may invalidate
warranty.
This instruction details the basic
settings that must be completed before
the actuator is put into service.
WARNING:
Electrical operation
must not take place until the basic
settings have been made and checked.
The basic settings affect the correct
operation of the valve by the actuator.
If the actuator has been supplied with
the valve, the valvemaker or supplier
may have already made these settings.
WARNING:
Settings and Operation
must be verified by electric operation
and a functional test of the actuated
valve.
THIS PUBLICATION PROVIDES
INSTRUCTION ON MAKING THE
BASIC SETTINGS ONLY.
For instruction on control and
indication settings and for
information on diagnostics refer
to PUB021-059.
7.1 Connecting to the Actuator
The BTST is shown below. It is
identifiable by the clear symbols and
clear seal between the casings.
The infrared only tool has yellow
symbols and yellow seal between
the casings. Both tools have a yellow
background on their keys.
The BTST with the relevant navigation
and configuration keys is shown below.
Up
Down
Back
Select/
Save
Right/
Increase
Left/Decrease
Summary of Contents for Skilmatic SI 3
Page 39: ...39...