SI manual – Section: Basic Settings for Commissioning
Each actuator is built in the factory to
be either Normally Closed, Normally
Open or Stayput depending on what
configuration was ordered.
Consult the factory if this configuration
needs to be changed as it cannot be
done through software alone.
7.5 Setting the Close Limits
The close settings are displayed on
lines 1/12 to 6/12.
1/12. Action
The actuator can be configured to
close on pressure (hydraulic or spring)
for seating valves or Limit for non-
seating valves.
The actuator will stop at the
mechanical end stop if set to Pressure
and the electrical limit if set to Limit.
Press
to select Close Action
function. Use or to check
function setting. Press
to set.
2/12. Pressure Limit
This setting is the maximum cut-off
pressure in a normally open actuator
while traveling from the closed
electrical limit to the closed mechanical
end stop. The value set is a % of the
maximum system pressure, which is
limited by the pressure relief valve.
Press
to select the Pressure Limit
function. Use key to decrease value
and key to increase value.
Press
key to set.
3/12. Pressure Mid
This setting is the maximum cut-off
pressure in a normally open actuator
while traveling in mid-travel between
the open and closed electrical limits
while closing. This can be set between
0% and 100%. When set at 0% the
Pressure Mid value is set at the same as
the Pressure Limit. When set between
1% to 100%, the Pressure Mid value is
a proportion of the maximum system
pressure.
WARNING:
If the actuator fails to
complete a close or open operation
due to the set pressure being reached,
it may indicate a valve and/or process
problem or change. It is the responsibility
of the user to ensure the valve and
process conditions are within the
specified operational limits.
4/12. Semi Auto Setup
When this setting is on, it allows the
closed electrical limit to be set by
moving the actuator to the closed
mechanical end stop and storing its
position. The electrical limit will then
be scaled in 1% between the closed
and open end stops.
When this setting is off, it allows the
closed electrical limit to be manually
set by moving the actuator to the
desired position and then storing it.
The electrical limit needs to be set in
from the mechanical end stop by at
least 1%.
5/12. Set Limit
Press
to set the closed limit.
If Semi Auto Setup is turned on the
following instruction will be shown:
Move to closed limit.
Move the actuator to the closed
mechanical end stop using the local
controls and select OK.
If Semi Auto Setup is turned off the
following instruction will be shown:
Move to closed limit
and allow for overrun.
Move the actuator to the closed
position where the electrical limit
needs to be set using the local controls
and select OK.
6/12. Sensor Position
This is a live reading of the position
sensor which can be viewed when
setting the limits. This setting is non-
adjustable.