SI manual – Section: Maintenance and Troubleshooting
33
9. Maintenance and
Troubleshooting
9.1 General Maintenance
Every Rotork actuator has been fully
tested before dispatch to give years of
trouble-free operation providing it is
installed, sealed and commissioned in
accordance with the instructions given
in this publication.
The SI actuator’s non-intrusive
enclosure provides complete protection
for the actuator components. Covers
should not be removed for routine
inspection as this may be detrimental
to the future reliability of the actuator.
The enclosure contains no user
serviceable components.
All electrical power supplies to the
actuator must be isolated before any
maintenance or inspection is carried out.
Electrical supplies must be isolated
before actuator covers are removed
If the motorised valve is rarely
operated, a routine operating schedule
should be set up, which may include
partial stroking the actuator at regular
intervals.
Routine maintenance should include
the following:
• Check actuator valve fixing bolts for
tightness.
• Ensure valve stems and drive nuts
are clean and properly lubricated.
• Check the control module enclosure
for external damage, loose or
missing fasteners.
• All external fasteners must be
tightened to 40 Nm (30 lbf.ft)
• Ensure there is not an excessive
build-up of dust or contaminant on
the actuator.
• Check for any loss of hydraulic fluid.
This can be done by removing the
hydraulic fluid fill plug when the
electrical power is removed from
the actuator. The fluid level should
be within 50 mm (2”) of the fluid fill
plug sealing face of the tank. If it is
necessary to top up hydraulic fluid
ensure that the correct type of fluid
is used. See actuator name plate.
It may be necessary to remove the
actuator from the valve to carry
this out.
• If the fluid level is low, visually
inspect the actuator and tighten
any hydraulic fittings that may be
leaking.
• Check the operating speeds in both
the open and closed directions by
conducting a full-stroke test.
• Fully open the actuator and turn
the red local control knob to stop.
Leave the actuator for 30 minutes
and check that the actuator has not
drifted off the open limit.
Routine maintenance should include
the following after five years of service:
• The hydraulic fluid and filter should
be replaced (Refer to Weights and
Measures, section 11, for the volume
of fluid required).
• The actuator seals should be
replaced.
Summary of Contents for Skilmatic SI 3
Page 39: ...39...