Smart Positioner
YT-2500 / 2550 / 2501 Series
Product Manual
Ver. 1.34
45
9.6.1
Dead-Zone (dEAdZONE, %)
Dead-Zone indicates the percentage of error allowance. When AUTO 2 or AUTO 3 calibration are done,
this value would be set automatically and moderately. But if hunting still occur after AUTO 2 or AUTO
3 calibration for the reason such as high level of packing friction, increasing the value of Dead-Zone
can stable the valve operation.
<ENTER>
3 seconds
→
<ENTER>
→
<ENTER>
→
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
<ENTER>
→
<ESC>
3 times
→
9.6.2
P1 Value (KP1)
P value indicates the ratio of the compensation signal based on the percentage of error allowance. As
the value increase, the positioner finds the target point quickly, but it is more likely to have hunting. As
the value decrease, the stability of the positioner is higher, but it finds the target point slowly. But these
values are applicable for only when input signal is increasing.
<ENTER>
→
<ENTER>
→
<UP>/<DOWN>
<ENTER>
→
Press <UP> or
<DOWN> button
if the above is not
displayed.
<ESC>
3 times
→