1.3 RMS Data Logger
Order code: RMS-LOG-L or RMS-LOG-868 or RMS-LOG-915
The data logger carries out measurements in a fixed interval, saves all measured data and sends it to the
database by radio or Ethernet link. Should the connection be lost, the logger stores the data intermediately to
protect data integrity and fills up the data gaps when the connection has been restored. The measurement
parameters depend on the connected probe; two different parameters can be measured at the same time. The
device has a battery so that logging of measured data is also ensured in the event of a failure in the external
power supply.
The data logger provides the following basic functions:
o
Logging of the measured values of the connected probe
o
Data logging of up to 44,000 pairs of measured values
o
Transfer of the recorded data to the RMS software
o
Calibration and adjustment of the probe
o
Firmware update
1.4 RMS Display
Order code: RMS-D-L
The RMS Display is a freely configurable device. The unit can be placed anywhere, not necessarily next to the
measurement point. The display allows the visualisation of measurement values, conditions and alarms of
devices within the RMS software.
The RMS Display provides the following basic functions:
o
Display of up to 4 measuring values and their trends
o
Actualisation every 10s
o
Display of errors, alarms, warnings and notifications
o
Display of the time
The RMS display will show 2 measurement values at a time. Should more than 2 measurement values be
selected, then the display will automatically switch every 5 seconds between the measurement values.
Under each measurement value, the name of the measuring point will be indicated. The parameter will be
shown on the right, next to the measurement value
Various notifications can also be displayed:
o
Error: E
o
Alarm: A
o
Warning: W
o